Protection spark
gaps form an important part of series
compensation schemes in high voltage
transmission and distribution networks.
Their primary function is to safeguard the
series capacitors from transient over
voltages. In the event of fault, the line
current may momentarily increase and the
corresponding voltage across the capacitor
banks may exceed the short time over-voltage
limit . The spark gap, which is connected in
parallel with the bank is set to spark over
when the voltage across the bank exceeds the
permissible level. Thus the spark gap acts
as a bypass for the capacitor during faults.
Technical Parameters
Type
of Gap : Non Self Extinguishing
Application : For capacitor bank protection
In 132 KV/220 KV series
compensation scheme
Electrode System : Main gap
Range of Flashover setting : 55 KV to 120 Kv
Short time rating : 15 KA for 0.2S
Deionization time : 0.4 sec. For 80%
withstand voltage
Tolerance in flashover voltage : +/-5%
Type pf terminal : Stud type
Material of terminal Brass
Type of enclosure : Aluminum
Insulation between enclosure and Porcelain
Insulator
Insulated Platform