25KV AC 50Hz Pole Outdoor Vacuum Interrupter Type PVTI

Technical Parameters

Value

Rated operating voltage

25kV

Rated insulation class

52kV

Rated normal current

800A

Rated power frequency withstand voltage

95kV

Rated lightning Impulse withstand voltage

250kVp

Rated short time withstand current

8kA for 3 secs

Rated short circuit making current

20kAp

Rated duty cycle

CO-15sec-CO

Rated aux. supply for spring charging motor

110VDC

Motor rating

700W

Rated supply voltage for trip/close coils

110VDC

Power required for trip/close coil

275W

Applicable standards

IEC62271-100

RDSO specification

ETI/PSI/167 (09/97)

Auxiliary Switch

6NO + 6NC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   Service environmental conditions:

Maximum ambient air temperature

45°C

Minimum ambient air temperature

0°C

Average ambient air temperature over a period of 24hrs

35°C

Maximum relative humidity

100%

Annual rainfall range

1750mm to 862530mm

Number of thunderstorm days per annum

85 (max)

Number of dust storm days per annum

35 (max)

Number of rainy days per annum

120 (max)

Maximum basic wind pressure

200 Kg/Sqm

Altitude

Not Exceeding 1000m

Pollution level

Heavily Polluted